Fixed Orifice Fed Indoor Coil
Charging by Superheat Table
Cooling Mode
| Indoor | Outdoor Ambient | ||||||||||||||
| WB | DB | & R/H |
55 | 60 | 65 | 70 | 75 | 80 | 85 | 90 | 95 | 100 | 105 | 110 | 115 |
| 56 | 60 65 70 75 80 |
78 57 41 29 20 |
17 18 19 21 22 |
12 14 15 16 18 |
8 9 10 11 14 |
5 5 5 7 9 |
5 5 5 5 5 |
5 5 5 5 5 |
5 5 5 5 5 |
5 5 5 5 5 |
5 5 5 5 5 |
5 5 5 5 5 |
5 5 5 5 5 |
5 5 5 5 5 |
5 5 5 5 5 |
| 58 | 60 65 70 75 80 |
89 67 49 34 24 |
22 23 23 23 24 |
18 18 18 19 20 |
13 14 14 14 16 |
9 9 10 10 12 |
5 5 5 6 8 |
5 5 5 5 5 |
5 5 5 5 5 |
5 5 5 5 5 |
5 5 5 5 5 |
5 5 5 5 5 |
5 5 5 5 5 |
5 5 5 5 5 |
5 5 5 5 5 |
| 60 | 65 70 75 80 85 |
76 57 41 30 21 |
24 25 26 27 28 |
20 21 22 23 25 |
16 17 18 19 21 |
8 9 10 12 14 |
5 5 6 8 10 |
5 5 5 5 6 |
5 5 5 5 5 |
5 5 5 5 5 |
5 5 5 5 5 |
5 5 5 5 5 |
5 5 5 5 5 |
5 5 5 5 5 |
5 5 5 5 5 |
| 62 | 65 70 75 80 85 |
85 64 49 36 26 |
21 24 26 26 27 |
17 20 22 22 24 |
13 16 18 19 20 |
9 12 15 15 17 |
5 8 11 12 13 |
5 5 7 8 10 |
5 5 5 5 6 |
5 5 5 5 5 |
5 5 5 5 5 |
5 5 5 5 5 |
5 5 5 5 5 |
5 5 5 5 5 |
5 5 5 5 5 |
| 64 | 70 75 80 85 90 |
72 56 42 31 24 |
30 31 32 33 34 |
26 28 29 30 31 |
23 24 25 26 27 |
19 21 22 23 24 |
15 17 19 20 21 |
12 14 16 17 18 |
8 10 13 13 14 |
5 7 9 10 11 |
5 5 6 7 8 |
5 5 5 5 5 |
5 5 5 5 5 |
5 5 5 5 5 |
5 5 5 5 5 |
| 66 | 70 75 80 85 90 |
81 63 48 36 28 |
32 33 35 35 36 |
29 29 32 32 33 |
26 26 29 29 30 |
22 23 26 26 27 |
19 20 23 23 24 |
15 16 20 20 21 |
12 13 17 17 18 |
9 13 14 14 15 |
5 10 11 11 12 |
5 7 8 8 9 |
5 5 5 5 6 |
5 5 5 5 5 |
5 5 5 5 5 |
| 68 | 70 75 80 85 90 |
90 70 54 42 32 |
35 36 36 38 39 |
32 33 34 35 36 |
29 30 31 32 33 |
26 26 28 30 31 |
23 23 25 27 28 |
09 20 23 24 25 |
16 17 20 21 22 |
13 14 17 18 19 |
10 11 14 15 17 |
7 8 12 13 14 |
5 5 9 10 11 |
5 5 6 7 8 |
5 5 5 5 5 |
| 70 | 75 80 85 90 |
79 62 48 38 |
38 38 41 42 |
36 36 38 39 |
33 33 36 37 |
30 31 33 34 |
27 28 30 32 |
24 26 28 29 |
21 23 25 27 |
19 21 23 24 |
16 18 20 21 |
13 16 18 19 |
10 13 15 16 |
7 11 13 14 |
5 8 10 11 |
| 72 | 75 80 85 90 95 |
88 68 54 42 33 |
41 41 42 43 43 |
38 38 40 40 40 |
36 36 38 38 38 |
33 34 35 35 35 |
31 31 33 33 33 |
28 29 30 30 31 |
26 27 28 29 29 |
23 24 25 26 27 |
20 22 23 24 24 |
18 20 21 21 22 |
15 17 18 19 20 |
13 15 16 17 18 |
10 13 13 14 15 |
| 74 | 75 80 85 90 95 |
96 76 60 48 38 |
43 43 44 44 45 |
41 41 41 42 43 |
39 39 39 40 40 |
36 37 37 38 38 |
34 35 35 35 36 |
32 32 33 33 33 |
29 30 31 31 31 |
27 28 29 29 29 |
25 26 26 26 27 |
22 24 24 24 25 |
20 22 22 22 22 |
18 19 20 20 20 |
15 18 18 18 18 |
| 76 | 80 85 90 95 |
84 67 54 43 |
45 46 47 49 |
43 44 46 47 |
42 42 44 45 |
40 41 42 43 |
38 39 40 41 |
36 37 38 40 |
34 35 36 38 |
32 33 34 36 |
30 31 32 34 |
28 29 31 32 |
27 27 29 31 |
25 25 27 29 |
23 23 25 27 |
| 78 | 80 85 90 95 |
92 74 59 48 |
48 48 50 51 |
46 47 48 50 |
44 45 47 49 |
43 43 45 47 |
41 41 44 46 |
39 40 42 45 |
38 38 41 43 |
36 36 39 42 |
34 34 37 41 |
33 33 36 39 |
31 31 34 37 |
29 30 33 36 |
27 28 31 35 |
| 80 | 85 90 95 |
80 65 53 |
50 51 53 |
49 50 51 |
47 48 50 |
46 47 49 |
44 46 47 |
43 44 46 |
41 43 44 |
40 41 43 |
39 40 41 |
37 39 40 |
36 37 39 |
34 36 37 |
33 34 36 |
| Notes: | All information based on 400 CFM/Ton Charge within 2ºF ± of superheat indicated. Recommended minimum superheat is 5°F. Superheat temperature measurements should be taken within 3 feet of the compressor suction line connection. R/H - Approximate % of indoor relative humidity. WB - Indoor wet bulb temperature °F. DB - Indoor dry bulb temperature °F. |